Signet SmartPro 9900 Multi-Parameter Transmitter

Pick your application and the 9900 will change to provide flow, pH, ORP, level, temperature, pressure, conductivity, resistivity, or salinity.  All controlled by the sensor.

The 9900 provides:

The 9900 accepts the Signet digital S3L signal or frequency signal from a flow sensor.

Paddlewheel and flow through sensors provide a frequency signal used by the 9900.  Magnetic flow sensors provide both a frequency and a S3L signal.

Pressure sensors, temperature sensors and level sensors provide the S3L signal.  pH and ORP will provide a S3L signal when using the 2750 electronics.

Conductivity / Resistivity sensors 2819-2823 and 2839-2842 do require a plug-in module 3-9900.394.  As an option 2919-2823 sensors can be directly connected to  2850 electronics without the need of this plug-in module. 

The 9900 can be configured to accept outside vendor 4-20mA signal when using A to D converter # 8058-1 or 8058-2.  Converts 4-20mA to digital S3L signal.  AKA I-Go

  brochure                        data sheet              Instruction Manual

Hyper link for additional details http://www.gfsignet.com/go/D30260D719993E1D3450D2020CE709C0

Signet Index                     KTH Home Page

GF Signet 9900 Transmitter component compatibility selections

Use the following graphics as an outline of sensor / transmitter compatibility.  This information is also available on the data sheet file.  Please contact KTH Sales with questions of other options. 


Flow Systems - Level Systems - Temperature Systems - Pressure Systems


pH / ORP


Conductivity / Resistivity / Salinity

Sensors for Signet conductivity transmitters.

Conductivity / Resistivity sensors are designed to provide versatile installation and accurate sensing across a broad dynamic range.  Accuracy of +/-2% for reading range and temperature indication using a Platinum RTD sensor.  Standard material is 316SS with options of titanium, Hastelloy C and Monel.  Easily mounts with 3/4" NPT fitting inline or couplings for submersible installations.  

Download specifications or installation manual for 2819 - 2823 sensors.  Sensor for sanitary applications are also available in stainless or titanium - contact KTH Sales

Range ÁS Model Prices example of range
0.055 to 100 (18.2Mohm-10Kohm) 3-2819 $ 310.00 DI water to bottled water
1 to 1000 (0.5 -500 ppm) 3-2820 $ 310.00 rinse water to drinking water
10 to 10,000 (5 - 5,000 ppm) 3-2821 $ 310.00 drinking water
100 to 200,000 (50-100,000 ppm) 3-2822 $ 517.00 bottled water to chemicals
200 to 400,000 (100-200,000 ppm) 3-2823 $ 614.00 waste water to chemicals

 All signet above sensors are compatible 8860, 5800CR, 5900 and  8850 (except when using integral kit).  Also compatible with 3-9900-1P when supplied with 3-9900.394 module. 

 

PEEK Body Sensors with dual threaded connections for water applications.  Style 2839, 2840, 2841 and 2842 provide a compact design ideal for submersible or inline piping. The upper 3/4" thread is used for submersible with the lower 3/4 NPT thread for inline piping.  All feature a triple orifice flow-through design to minimize clogging and bubble entrapment.

Download specifications 

Range ÁS Model Prices example of range
0.055 to 100 (18.2Mohm-10Kohm) 3-2839 $ 269.00 DI water to bottled water
1 to 1000 (0.5 -500 ppm) 3-2840 $ 269.00 rinse water to drinking water
10 to 10,000 (5 - 5,000 ppm) 3-2841 $ 269.00 drinking water
100 to 200,000 (50-100,000 ppm) 3-2842 $ 363.00 bottled water to chemicals

Above are compatible with 8850, 8860, 5800CR and 5900 instruments.  Also compatible with 3-9900-1P when supplied with 3-9900.394 module. 

 

Signet Index                      KTH Home Page